Element 5.14

Heat pumps in every climate

Sheet
5.14
Chapter
5 Energy
State
Drafted
Release
16 November 2026
Editor
Contributed by Praecise as open research
Reviewers
To be named at review
Safety
S3, as the chapter
Licence
CC BY-SA 4.0
Resources
8

The element

Requirement

Where a community heats or cools with heat pumps, each machine is sized to the measured heat loss or gain of its building, runs at a seasonal efficiency well above resistance heating in the coldest month, and uses a refrigerant whose charge, location and handling meet the safety standard in force. Element 5.5 sets heat pumps as an option; this element covers how to choose, check and run them in each climate.

How to tell

Heat delivered and electricity used are both metered, so a seasonal performance factor can be computed for each unit OpenEnergyMonitor. As a field benchmark, a four-year test of 77 heat pumps in existing German houses found seasonal performance factors of 2.6 to 5.4, averaging 3.4 for air-to-water and 4.3 for ground-source units, with electric back-up rods supplying 1.3% of the electricity of air-to-water units Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. A unit well below that range points to a fault: the same study found frequent oversizing and very high switching rates. Refrigerant charge and placement are checked against IEC 60335-2-40 for household units Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022) and the ISO 5149 series for larger systems ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteria.

Options

Air-source. No ground works needed. Field data pooled from several countries show efficiency well above fossil and resistance heating below 0 degrees C, and standard units suit winters that rarely fall below -10 degrees C Coming in from the cold: Heat pump efficiency at low temperatures.

Ground-source. Higher efficiency in the field (4.3 against 3.4 on average in the German study) Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings, at the cost of boreholes or trenches. The same ground loop can cool in summer with only a circulation pump; Annex 80 gives specific borehole cooling capacities of 22 to 63 W per metre in Cyprus, Germany and Japan Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80).

Water-source. A lake, river or aquifer replaces the ground loop; Annex 80 cites closed water loops at 35 to 117 W per metre of pipe, with open loops limited by aquifer yield and abstraction rules Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80).

Natural refrigerants. The 2022 revision of IEC 60335-2-40 allows up to 988 g of propane (R290) in a split system with added protection such as leak detection and shut-off valves, against 334 g before; each country decides when to adopt it Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022).

Settled, open, contested

Settled. Heat pumps beat resistance heating at the appliance level in all the climates measured Coming in from the cold: Heat pump efficiency at low temperatures. Building age does not decide performance; design and installation do Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. Refrigerant work is at safety level S3: flammable and high-pressure refrigerants are handled only by certified people, and this page gives no procedure.

Open. How much back-up heat the coldest climates need, and the role of hybrid systems where temperatures approach -30 degrees C Coming in from the cold: Heat pump efficiency at low temperatures.

Contested. Propane or synthetic low-GWP refrigerants. Propane has very low climate impact and is now allowed in larger charges with safeguards Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022); synthetic refrigerants are less flammable and familiar to installers, while HFCs fall under the Kigali phase-down The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties.

The four stages

Resources at each stage

What changes between 30 adults and 300 people

For 30 adults, one unit per building, or one ground loop for a shared building, is enough and the metering is simple. For 300 people the winter electrical peak becomes the sizing problem: the IEA notes a household's peak can nearly triple with a heat pump and no efficiency upgrade The Future of Heat Pumps, so insulation and a shared ground or water source, or a heat network (see the heat networks element), become worth comparing. Refrigerant handling then needs a named, trained person or a service contract.

Reference designs

Open for contributions Designs with drawings, specifications and a bill of materials. Add to it

Parts list

Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.

ResourceTypeOriginMaturitySafetyLicence, as stated at its source
Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildingsCase studyExternalReplicatedS0Not stated on the page opened
Coming in from the cold: Heat pump efficiency at low temperaturesPaperExternalReplicatedS0Unspecified
Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80)FrameworkExternalReplicatedS0© Copyright Institute of Building Research & Innovation 2024. No part of this publication may be reproduced without prior written permission.
The Future of Heat PumpsPaperExternalEstablishedS0CC BY 4.0
Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022)StandardExternalEstablishedS3Not stated on the page opened
ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteriaStandardExternalEstablishedS3Not stated on the page opened
OpenEnergyMonitorToolExternalNot assessedS2Not stated on the pages opened
The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the PartiesFrameworkExternalEstablishedS0Not stated on the page opened

Depends on, and completes

Depends on 5.1, 5.2, 5.5, 6.3.

It is one of 23 elements that complete Energy.

The standing questions

Who pays the first cost and who gains from lower bills. Who is certified to touch the refrigerant circuit. Who decides when an old unit is replaced under a tightening HFC schedule.

Environments

Arctic cold. Efficiency falls but stays above resistance heating near -30 degrees C; back-up heat may be needed Coming in from the cold: Heat pump efficiency at low temperatures. Temperate forest. The German field test is the reference: 2.6 to 5.4 Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. Hot deserts and humid tropics. The same machines run as air conditioners; the Kigali Amendment allows an exemption for high-ambient-temperature countries under criteria the parties set The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties. No field efficiency source was opened. Islands and coasts. Sea or lake water can serve as the source or sink (water-source option) Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80). No source found on salt corrosion of outdoor units. High altitude, flood plains. No source found.