Element 5.14
Heat pumps in every climate
- Sheet
- 5.14
- Chapter
- 5 Energy
- State
- Drafted
- Release
- 16 November 2026
- Editor
- Contributed by Praecise as open research
- Reviewers
- To be named at review
- Safety
- S3, as the chapter
- Licence
- CC BY-SA 4.0
- Resources
- 8
The element
- Requirement
Where a community heats or cools with heat pumps, each machine is sized to the measured heat loss or gain of its building, runs at a seasonal efficiency well above resistance heating in the coldest month, and uses a refrigerant whose charge, location and handling meet the safety standard in force. Element 5.5 sets heat pumps as an option; this element covers how to choose, check and run them in each climate.
- How to tell
Heat delivered and electricity used are both metered, so a seasonal performance factor can be computed for each unit OpenEnergyMonitor. As a field benchmark, a four-year test of 77 heat pumps in existing German houses found seasonal performance factors of 2.6 to 5.4, averaging 3.4 for air-to-water and 4.3 for ground-source units, with electric back-up rods supplying 1.3% of the electricity of air-to-water units Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. A unit well below that range points to a fault: the same study found frequent oversizing and very high switching rates. Refrigerant charge and placement are checked against IEC 60335-2-40 for household units Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022) and the ISO 5149 series for larger systems ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteria.
- Options
Air-source. No ground works needed. Field data pooled from several countries show efficiency well above fossil and resistance heating below 0 degrees C, and standard units suit winters that rarely fall below -10 degrees C Coming in from the cold: Heat pump efficiency at low temperatures.
Ground-source. Higher efficiency in the field (4.3 against 3.4 on average in the German study) Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings, at the cost of boreholes or trenches. The same ground loop can cool in summer with only a circulation pump; Annex 80 gives specific borehole cooling capacities of 22 to 63 W per metre in Cyprus, Germany and Japan Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80).
Water-source. A lake, river or aquifer replaces the ground loop; Annex 80 cites closed water loops at 35 to 117 W per metre of pipe, with open loops limited by aquifer yield and abstraction rules Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80).
Natural refrigerants. The 2022 revision of IEC 60335-2-40 allows up to 988 g of propane (R290) in a split system with added protection such as leak detection and shut-off valves, against 334 g before; each country decides when to adopt it Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022).
- Settled, open, contested
Settled. Heat pumps beat resistance heating at the appliance level in all the climates measured Coming in from the cold: Heat pump efficiency at low temperatures. Building age does not decide performance; design and installation do Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. Refrigerant work is at safety level S3: flammable and high-pressure refrigerants are handled only by certified people, and this page gives no procedure.
Open. How much back-up heat the coldest climates need, and the role of hybrid systems where temperatures approach -30 degrees C Coming in from the cold: Heat pump efficiency at low temperatures.
Contested. Propane or synthetic low-GWP refrigerants. Propane has very low climate impact and is now allowed in larger charges with safeguards Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022); synthetic refrigerants are less flammable and familiar to installers, while HFCs fall under the Kigali phase-down The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties.
The four stages
Learn: what heat pumps do and cost The Future of Heat Pumps; how they behave in cold Coming in from the cold: Heat pump efficiency at low temperatures. Design: heat loss first (6.3), then size; avoid oversizing Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings; check refrigerant against Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022) and ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteria. Build: a certified installer handles refrigerant and electrical work. Deploy: meter heat and electricity and compute the seasonal figure OpenEnergyMonitor.
Resources at each stage
1 Learn
Understand
- Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings Case study, S0
- Coming in from the cold: Heat pump efficiency at low temperatures Paper, S0
- Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80) Framework, S0
- The Future of Heat Pumps Paper, S0
- The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties Framework, S0
2 Design
Size and choose
- Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings Case study, S0
- Coming in from the cold: Heat pump efficiency at low temperatures Paper, S0
- Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80) Framework, S0
- The Future of Heat Pumps Paper, S0
- Adoption of long-awaited standard for flammable refrigerants (IEC 60335-2-40, approved 2022) Standard, S3
- ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteria Standard, S3
- The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties Framework, S0
3 Build
Build or obtain
4 Deploy
Install, run and measure
- Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings Case study, S0
- Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80) Framework, S0
- ISO 5149-1, Refrigerating systems and heat pumps: Safety and environmental requirements, Part 1: Definitions, classification and selection criteria Standard, S3
- OpenEnergyMonitor Tool, S2
What changes between 30 adults and 300 people
For 30 adults, one unit per building, or one ground loop for a shared building, is enough and the metering is simple. For 300 people the winter electrical peak becomes the sizing problem: the IEA notes a household's peak can nearly triple with a heat pump and no efficiency upgrade The Future of Heat Pumps, so insulation and a shared ground or water source, or a heat network (see the heat networks element), become worth comparing. Refrigerant handling then needs a named, trained person or a service contract.
Reference designs
Open for contributions Designs with drawings, specifications and a bill of materials. Add to it
Parts list
Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.
The standing questions
Who pays the first cost and who gains from lower bills. Who is certified to touch the refrigerant circuit. Who decides when an old unit is replaced under a tightening HFC schedule.
Environments
Arctic cold. Efficiency falls but stays above resistance heating near -30 degrees C; back-up heat may be needed Coming in from the cold: Heat pump efficiency at low temperatures. Temperate forest. The German field test is the reference: 2.6 to 5.4 Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings. Hot deserts and humid tropics. The same machines run as air conditioners; the Kigali Amendment allows an exemption for high-ambient-temperature countries under criteria the parties set The Kigali Amendment (2016): the amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties. No field efficiency source was opened. Islands and coasts. Sea or lake water can serve as the source or sink (water-source option) Resilient Cooling of Buildings: Project Summary Report (IEA EBC Annex 80). No source found on salt corrosion of outdoor units. High altitude, flood plains. No source found.
Safety
State and evidence
Drafted
An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.
Evidence from a real place or system is recorded here, with what did not work. What the states mean
History
- Drafted in the release of 16 November 2026.