Test instruments and measurement categories

Sheet
9.9
Chapter
9 Manufacturing and repair
State
Drafted
Release
16 November 2026
Editor
Contributed by Praecise as open research
Reviewers
To be named at review
Safety
S3, as the chapter
Licence
CC BY-SA 4.0
Resources
5

The element

Requirement

Every instrument and every lead used on a mains circuit carries a measurement category (CAT) and voltage rating equal to or higher than the point where it is used, and is used only by people trained for that work. Instruments with no CAT rating are kept off the mains. Circuits that are not mains but may have very high available energy have no standard transient levels, and the guide states their insulation and short-circuit requirements need analysis (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)). This page gives no measuring procedure.

How to tell

The terminals of the instrument are marked with a CAT rating and a voltage to earth, as IEC 61010 requires (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)). A trade association guide summarises the categories (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)):

  • CAT II: socket outlets and similar points, appliances and portable tools; short-circuit currents typically below 10 kA.
  • CAT III: the distribution part of the building, including distribution boards, cables, lighting, fixed motors and photovoltaic panels; typically up to 50 kA.
  • CAT IV: from the supply source to the first isolator, including the tariff meter and service fuse; typically above 50 kA, where an accidental short can cause an extremely dangerous arc flash.

Voltage ratings are normally 50, 100, 150, 300, 600 or 1,000 V phase to earth (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Options

A rated multimeter or two-pole voltage detector. Choose for the highest category the community will meet. A CAT III 250 V meter must not be used on CAT IV circuits at any voltage; category and voltage cannot be traded off unless the instrument or its instructions say so; detachable probe insulators can change a tester's rating from CAT II to CAT III or IV (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Leads and accessories. They need ratings equal to or higher than the location (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Unrated instruments. Logic analysers, bench meters and open tools such as sigrok-supported devices are for low-voltage electronics (sigrok). The guide states that an instrument with no CAT rating must not be connected to the mains even if its voltage rating exceeds the supply (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Fixed monitoring. Permanently installed meters on main circuits, fitted by an electrician (OpenEnergyMonitor).

Settled, open, contested

Settled. Match the instrument and leads to the category and voltage (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Open. Whether CAT ratings on low-cost instruments have been independently checked; the guide notes some makers overlook the requirement to warn against mains use on unrated instruments (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Contested. No disagreement found in the sources read.

What changes between 30 adults and 300 people

For 30 adults, one CAT III or CAT IV rated meter and one voltage detector held by the trained person. For 300 people, a tool store with a register of instruments, their ratings and their condition, and named people authorised to use them on each category.

Reference designs

Open for contributions Designs with drawings, specifications and a bill of materials. Add to it

Parts list

Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.

ResourceTypeOriginMaturitySafetyLicence, as stated at its source
Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)GuideExternalEstablishedS3Not stated on the page opened
IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipmentStandardExternalEstablishedS3Not stated on the page opened
Lessons In Electric CircuitsGuideExternalEstablishedS0Creative Commons License (variant not named on the page)
OpenEnergyMonitorToolExternalNot assessedS2Not stated on the pages opened
sigrokToolExternalEstablishedS0GNU GPL, version 3 or later

Depends on, and completes

Depends on 5.4, 5.7.

It is one of 34 elements that complete Manufacturing and repair.

The standing questions

Who owns and maintains the instruments. Who is trained to use them on live circuits. Who decides who may.

Environments

No source found that changes measurement categories by setting. Photovoltaic arrays, wherever they stand, are CAT III points (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Safety

State and evidence

Drafted

An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.

Evidence from a real place or system is recorded here, with what did not work. What the states mean

History