The element

Requirement

A battery store is sited, separated and protected so that a failure in one unit does not spread to other units, to buildings or to people, and the installation meets the energy storage standards and fire rules that apply where it stands. Fire services know it is there. This page gives no procedure for installation, fire-fighting or testing; those belong to qualified people and the authority having jurisdiction.

How to tell

The battery system is certified as a system and its installation follows a named standard. Internationally, IEC 62933-5-2 sets safety requirements for battery energy storage as a system across its whole life cycle, from design to end of service life; its second edition was published on 9 December 2025 (IEC 62933-5-2:2025 Electrical energy storage (EES) systems - Part 5-2: Safety requirements for grid-integrated EES systems - Electrochemical-based systems). The cells meet IEC 62619 for lithium in stationary use (EN IEC 62619:2022 Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applications). In North America, NFPA 855 is the installation standard for stationary energy storage (NFPA 855, Standard for the Installation of Stationary Energy Storage Systems), and UL 9540A tests how thermal runaway propagates at cell, module, unit and installation level; it is the only consensus standard NFPA 855 cites for large-scale fire testing (UL 9540A Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems). A building fire risk assessment covers the room or enclosure (Fire safety risk assessment: 5-step checklist).

Options

Outdoor enclosure or container, separated from buildings. EPRI's analysis of 150 incidents worldwide from 2018 to 2025 found indoor facilities overrepresented in failures and more damaged on average, and that propagation prevention within and between units is critical (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)).

Indoor room with barriers. Where indoor siting is unavoidable, EPRI states fire walls or other barriers can segment large facilities and limit propagation (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)). UL 9540A's 6th edition evaluates, for indoor systems, the effectiveness of building fire protection (UL 9540A Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems).

Non-flammable chemistries. A vanadium flow unit's data sheet states a non-flammable electrolyte and no fire suppression system required, with integrated secondary containment for the liquid (Invinity VS3-022 Vanadium Flow Battery (data sheet, January 2023)). The electrolyte is still a chemical hazard to contain.

Electrical protection on back-up circuits. Adding battery back-up changes the installation; in New South Wales it counts as an alteration that brings circuits up to current rules (Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025).

Settled, open, contested

Settled. Failures are rare and falling: EPRI states failures per deployed GWh fell 98% between 2018 and 2025, with 24 incidents in 634 GWh deployed in 2025, and that 93% of incidents caused no reported injury or death (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)). Propagation prevention is the core of design.

Open. EPRI notes about a fifth of incidents in its database were never reported in the media, so the record is incomplete (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)).

Contested. How strict siting rules should be for small community stores. EPRI calls for data-driven thresholds for precautions to avoid excessively burdening communities (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)). The opposing position, that every store should meet the full separations of the installation standard whatever its size, is the default wherever the authority having jurisdiction applies NFPA 855 or its equivalent unchanged (NFPA 855, Standard for the Installation of Stationary Energy Storage Systems).

The four stages

Resources at each stage

What changes between 30 adults and 300 people

For 30 adults, one store, preferably outdoors or in a separate enclosure, given EPRI's finding on indoor sites (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)). For 300 people, a store at settlement scale is a utility asset: EPRI compares its failure rate with large oil-filled transformers and notes that incident command and site control used for transformer fires largely apply (Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)). It needs a written emergency plan with the local fire service.

Reference designs

  • Reference design

    Invinity VS3-022 Vanadium Flow Battery (data sheet, January 2023)

    A maker's data sheet for a containerised vanadium flow battery of 230 kWh rated capacity. It states ambient operation from -5 to 45 °C, a maximum elevation of 2,000 m, more than 20,000 cycles at 0 to 100% depth of discharge, capacity degradation under 0.5% a year, maximum DC round-trip efficiency of 75%, a flooded weight of 24,600 kg, IP54 enclosure, non-flammable aqueous electrolyte, integrated secondary containment, listing to UL 1973 and testing to UL 9540A.

    External resource. Not made or verified by Public ProtocolMaturity: WorkingSafety S3CommercialListed 16 November 2026

Parts list

Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.

ResourceTypeOriginMaturitySafetyLicence, as stated at its source
Risk Factors and Failure Statistics of Lithium Ion BESS (EPRI White Paper 3002034920, October 2026)PaperExternalNot assessedS3© 2026 Electric Power Research Institute (EPRI), Inc. All rights reserved.
EN IEC 62619:2022 Secondary cells and batteries containing alkaline or other non-acid electrolytes - Safety requirements for secondary lithium cells and batteries, for use in industrial applicationsStandardExternalEstablishedS3Not stated on the page opened
IEC 62933-5-2:2025 Electrical energy storage (EES) systems - Part 5-2: Safety requirements for grid-integrated EES systems - Electrochemical-based systemsStandardExternalEstablishedS3Not stated on the page opened
Invinity VS3-022 Vanadium Flow Battery (data sheet, January 2023)Reference designExternalWorkingS3Not stated on the page opened
NFPA 855, Standard for the Installation of Stationary Energy Storage SystemsStandardExternalEstablishedS3Not stated on the page opened
Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025GuideExternalEstablishedS3Copyright © 2026
Fire safety risk assessment: 5-step checklistGuideExternalEstablishedS2Open Government Licence v3.0, except where otherwise stated
UL 9540A Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage SystemsStandardExternalEstablishedS3Not stated on the page opened

Depends on, and completes

Depends on 5.3.

It is one of 23 elements that complete Energy.

The standing questions

Who pays for separation and enclosures. Who briefs the fire service. Who decides where the store stands, and who lives nearest.

Environments

Islands and coasts. No source found. Arctic cold. No source found on fire behaviour in cold. Hot deserts. No source found beyond battery temperature limits (see the battery systems proposal). Tropical humid forest. No source found. Temperate forest. No source found on wildfire exposure of battery stores. High altitude. No source found. Flood plains. No source found; the flow unit's integrated secondary containment (Invinity VS3-022 Vanadium Flow Battery (data sheet, January 2023)) is relevant to spill risk but is not a flood rating. Other harsh settings. No source found.

Safety

State and evidence

Drafted

An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.

Evidence from a real place or system is recorded here, with what did not work. What the states mean

History