Public Protocol
Platform

Element 5.10

DC distribution and building-scale microgrids

Sheet
5.10
Chapter
5 Energy
State
Drafted
Release
16 November 2026
Editor
Contributed by Praecise as open research
Reviewers
To be named at review
Safety
S3, as the chapter
Licence
CC BY-SA 4.0
Resources
6

The element

Requirement

Where a community distributes direct current inside or between buildings, the DC system has protection, isolation and fault detection designed for DC, to a published rule set, by a qualified person. The shock principles of IEC 61140 apply whatever the current type (IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipment), so extra-low or direct current is no exemption. This page gives no wiring procedure.

How to tell

There is a single-line drawing showing every DC source, its protection and its isolator. The rule set followed is named. Protection against shock follows the common principles that IEC 61140 sets for installations whatever the current type (IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipment). Where DC and AC meet, residual current protection can detect the DC faults that inverters produce: a Type B device detects smooth DC residual current, which Types AC and A do not (Protection against earth faults with Residual Current Devices (Technical guide, 2015)). Solar arrays sit in measurement category III, so instruments used on them are rated for it (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Options

Extra-low-voltage DC (12, 24, 48 V). Fits a cabin, a cluster, lights and electronics. One maker's LFP batteries build banks of 12, 24 or 48 V, with at most 20 batteries and up to 102 kWh on one management system at 24 or 48 V (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)). Open charge controllers and management designs exist for this range (Libre Solar).

Building DC at higher voltage. Current/OS, a non-profit partnership of 160 partners in more than 30 countries, develops technical rules and a certification mark for hybrid AC/DC distribution; its site cites a 350 V DC network in an office building and 48 V DC for lighting, and states that it relies on ultra-fast protection for DC safety (Current/OS). Fits a new shared building whose loads are mostly DC: LED lighting, electronics, battery and solar.

AC distribution with DC-coupled storage. The conventional route: DC stays inside the battery and inverter, and buildings run AC. Fits where standard appliances and local electricians dominate.

Settled, open, contested

Settled. DC systems need DC-rated protection and isolation, and residual current devices chosen for the fault currents present (Protection against earth faults with Residual Current Devices (Technical guide, 2015)).

Open. A single international standard for building DC distribution. Current/OS publishes technical rules but the page opened does not state their licence or version (Current/OS).

Contested. DC or AC for a new small site. The domain 5 page already records both positions; this proposal adds that higher-voltage building DC has working projects such as the N470 road in Delft, operating since 2020 (Current/OS), but few local electricians are trained in it.

The four stages

Learn: Libre Solar, Current/OS. Design: choose the voltage level and rule set; the designer applies IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipment and selects residual current protection with Protection against earth faults with Residual Current Devices (Technical guide, 2015). Build: certified components (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet) shows the kind of system limits to check). Deploy: measurement with correctly rated instruments (Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)).

Resources at each stage

What changes between 30 adults and 300 people

For 30 adults, a 48 V system in one building is within the limits makers publish for single systems (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)). For 300 people, distance and power push towards higher DC voltage or AC between buildings; higher-voltage building DC is at the stage of operational projects and a certification scheme (Current/OS), so it needs a designer familiar with it.

Reference designs

  • Reference design

    Libre Solar

    Open designs for charge controllers and battery management systems, with a learning resource on how such systems work.

    External resource. Not made or verified by Public ProtocolMaturity: Not assessedSafety S2Listed 16 November 2026
  • Reference design

    12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)

    A maker's datasheet for lithium iron phosphate batteries that must be connected to an external battery management system. It states discharge from -20 to +50 °C, charging only from +5 to +50 °C, storage from -45 to +70 °C, cycle life to 80% capacity of 2,500 cycles at 80% depth of discharge and 5,000 at 50%, round-trip efficiency of 92% against 80% for an average lead-acid battery, capacity at -20 °C about half of that at 25 °C, and cell certifications including IEC 62619 and UL 9540A.

    External resource. Not made or verified by Public ProtocolMaturity: EstablishedSafety S3CommercialListed 16 November 2026

Parts list

Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.

ResourceTypeOriginMaturitySafetyLicence, as stated at its source
Protection against earth faults with Residual Current Devices (Technical guide, 2015)GuideExternalEstablishedS3Not stated on the page opened
Current/OSFrameworkExternalWorkingS3© Current/OS 2025
Guide to Overvoltage Categories & Measurement Categories (GAMBICA Technical Guide, version 1.1)GuideExternalEstablishedS3Not stated on the page opened
IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipmentStandardExternalEstablishedS3Not stated on the page opened
Libre SolarReference designExternalNot assessedS2BMS firmware: Apache-2.0, as stated in its repository
12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)Reference designExternalEstablishedS3Not stated on the page opened

Depends on, and completes

Depends on 5.2, 5.3, 5.4.

It is one of 23 elements that complete Energy.

The standing questions

Who can maintain a DC system when the person who designed it leaves. Who certifies it where national codes have little to say about DC. Who decides between AC and DC for a new building.

Environments

Islands and coasts. No source found. Arctic cold. Batteries that feed a DC bus may not accept charge in cold: one LFP maker states charging only from +5 °C (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)). Hot deserts. No source found beyond battery limits (discharge to +50 °C for the same product) (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)). Tropical humid forest. The same product is rated for humidity up to 95% non-condensing and enclosure class IP22, so condensing air needs a better enclosure (12,8 & 25,6 Volt Lithium-Iron-Phosphate Batteries Smart (datasheet)). Temperate forest. No source found. High altitude. No source found. Flood plains. No source found. Other harsh settings. No source found.

Safety

State and evidence

Drafted

An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.

Evidence from a real place or system is recorded here, with what did not work. What the states mean

History