Element 13.17
Small server rooms: temperature, humidity, dust and air quality
- Sheet
- 13.17
- Chapter
- 13 Digital infrastructure
- State
- Drafted
- Release
- 16 November 2026
- Editor
- Contributed by Praecise as open research
- Reviewers
- To be named at review
- Safety
- S2, as the chapter
- Licence
- CC BY-SA 4.0
- Resources
- 5
The element
- Requirement
Computing equipment is kept within its maker's stated range of temperature, humidity, altitude and air cleanliness, in a room that is secure and where batteries and power are installed safely.
- How to tell
- Inlet temperature and humidity are measured at the machines and stay inside the maker's range. As an example of what makers state, one common two-socket server allows 10 to 35 degrees C continuously, at 10 to 80 per cent relative humidity and a dew point no higher than 29 degrees C, below 950 m, with no direct sunlight on the equipment (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications).
- The air meets the maker's cleanliness limits. The same maker states ISO 14644-1 Class 8 air in a data centre, MERV11 or MERV13 filtration of incoming air, air free of conductive dust and zinc whiskers, no corrosive dust, any residual dust with a deliquescent point below 60 per cent relative humidity, and copper and silver coupon corrosion below 300 and 200 angstroms per month under ANSI/ISA-71.04-2013 (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications).
- Battery rooms follow the battery safety standards (IEC 62485-2:2010, Safety requirements for secondary batteries and battery installations, Part 2: Stationary batteries, IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium ion batteries).
- Options
- A cupboard or corner for 30 adults. One or two quiet machines in a ventilated space within the range above.
- A small room or micro data centre for 300 people. A rack, a UPS, cooling, a lock, and separate management networking (Ceph hardware recommendations).
- Use the expanded range with care. The example server allows 5 to 40 degrees C for up to 10 per cent of annual hours and minus 5 to 45 degrees C for up to 1 per cent, with performance possibly reduced (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications). This can reduce cooling needs in mild climates.
- The industry thermal guidelines. ASHRAE TC 9.9 publishes the Thermal Guidelines for Data Processing Environments that makers refer to. Its site refused access during this research, so its figures are not given here; read the maker's own range for each machine.
- Settled, open, contested
Settled. Makers state temperature, humidity and contamination limits, and operation outside them risks faults (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications). Open. Fire suppression for small server rooms: the NFPA 75 standard for protecting information technology equipment exists, but its page did not load and it is not described here. Noise limits and physical security for small rooms: no open source was found. Contested. How far to rely on expanded temperature ranges to save cooling energy.
The four stages
- Learn: read each machine's environmental specification (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications).
- Design: place the room away from flood and sun; plan airflow, filtration and a lock; keep batteries to their standards (IEC 62485-2:2010, Safety requirements for secondary batteries and battery installations, Part 2: Stationary batteries, IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium ion batteries).
- Build: install sensors for temperature and humidity at the machine inlets.
- Deploy: alert on limits (see Prometheus in the community cloud element); clean filters on a schedule.
Resources at each stage
2 Design
Size and choose
- Ceph hardware recommendations Guide, S1
- Dell EMC PowerEdge R740 Technical Specifications: environmental specifications Guide, S0
- IEC 62485-2:2010, Safety requirements for secondary batteries and battery installations, Part 2: Stationary batteries Standard, S3
- IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium ion batteries Standard, S3
3 Build
Build or obtain
4 Deploy
Install, run and measure
- Dell EMC PowerEdge R740 Technical Specifications: environmental specifications Guide, S0
- IEC 62485-2:2010, Safety requirements for secondary batteries and battery installations, Part 2: Stationary batteries Standard, S3
- IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium ion batteries Standard, S3
- Prometheus Tool, S0
What changes between 30 adults and 300 people
At 30 adults the machines can usually share a living or working space if they are quiet and within range. At 300 people a dedicated, locked, monitored room with filtered air and a UPS is needed, with written rules on who may enter.
Reference designs
Open for contributions Designs with drawings, specifications and a bill of materials. Add to it
Parts list
Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.
| Resource | Type | Origin | Maturity | Safety | Licence, as stated at its source |
|---|---|---|---|---|---|
| Ceph hardware recommendations | Guide | External | Established | S1 | Not stated on the page opened |
| Dell EMC PowerEdge R740 Technical Specifications: environmental specifications | Guide | External | Established | S0 | Not stated on the page opened |
| IEC 62485-2:2010, Safety requirements for secondary batteries and battery installations, Part 2: Stationary batteries | Standard | External | Established | S3 | Not stated on the page opened |
| IEC 62485-5:2020, Safety requirements for secondary batteries and battery installations, Part 5: Safe operation of stationary lithium ion batteries | Standard | External | Established | S3 | Not stated on the page opened |
| Prometheus | Tool | External | Established | S0 | Apache 2.0 License |
Depends on, and completes
Depends on 13.1.
It is one of 25 elements that complete Digital infrastructure.
The standing questions
Who can afford this: a cupboard costs nothing; a cooled room costs money and electricity. Who does the work: a keeper who reads the sensors and cleans filters. Who decides: where the room is and who has keys (15.3).
Environments
- High altitude: the example server derates its maximum temperature by 1 degree C per 175 m above 950 m in the 35 to 40 degree band, and by 1 degree C per 125 m above 950 m in the 40 to 45 degree band (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications).
- Tropical humid forest: humidity above 80 per cent or a dew point above 29 degrees C falls outside the standard range of the example server (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications); dehumidification may be needed.
- Hot deserts: dust must be filtered and conductive dust kept out; inlet air above 35 degrees C is outside the standard range (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications).
- Islands and coasts, industrial and polluted air: corrosive gases are measured with copper and silver coupons against the limits above (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications). No source opened addresses salt air directly.
- Arctic cold: the example server's standard range starts at 10 degrees C; minus 5 degrees C is allowed only for up to 1 per cent of annual hours (Dell EMC PowerEdge R740 Technical Specifications: environmental specifications). The room must be kept warm enough.
- Temperate forest, flood plains: no source found; on flood plains, place equipment above the flood level set in domain 20.
Safety
State and evidence
Drafted
An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.
Evidence from a real place or system is recorded here, with what did not work. What the states mean
History
- Drafted in the release of 16 November 2026.