Element 5.11

Electrical installations and protection against shock

Sheet
5.11
Chapter
5 Energy
State
Drafted
Release
16 November 2026
Editor
Contributed by Praecise as open research
Reviewers
To be named at review
Safety
S3, as the chapter
Licence
CC BY-SA 4.0
Resources
8

The element

Requirement

Every low-voltage installation the community builds protects people and livestock against electric shock and fire, follows the wiring rules in force where it stands, and is designed, inspected and signed off by a person qualified under those rules. This page states requirements and points to standards. It gives no wiring or testing procedure.

How to tell

The installation is certified under the national wiring rules by a qualified person, and the certificate matches what is built. The common international principles are in IEC 61140, the basic safety publication on protection against shock for installations and equipment at any voltage and for frequencies up to 1,000 Hz (IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipment). Wiring systems are selected and erected to IEC 60364-5-52, whose 2024 amendment revises the maximum permitted voltage drop and cable sizing where harmonic currents are present (IEC 60364-5-52:2009+AMD1:2024 Low-voltage electrical installations - Part 5-52: Selection and erection of electrical equipment - Wiring systems).

Socket circuits carry additional protection by a residual current device (RCD) of 30 mA or less. A maker's guide states that IEC 60364-4-41 requires this for socket circuits up to 20 A and for outdoor mobile equipment up to 32 A (Protection against earth faults with Residual Current Devices (Technical guide, 2015)). National codes go further: in the United Kingdom, BS 7671 requires it for socket-outlets up to 32 A, with a narrow exception that needs a documented risk assessment by a skilled person (Mythbusters 8: Socket-outlets must be protected by a 30 mA RCD (Wiring Matters, Issue 91, July 2022)).

Options

Earthing arrangement. The guide describes three systems. In TN systems the neutral is earthed at the source and exposed metalwork returns faults through a metal path. In TT systems protection relies on a local earth electrode; the earth path may be too resistive for a fuse or breaker to operate, so an RCD is compulsory for earth-fault protection. IT systems are kept for special uses where supply must continue after a first fault, such as operating theatres and mines (Protection against earth faults with Residual Current Devices (Technical guide, 2015)). A remote off-grid site often has no supplier earth, which makes the TT case common; the choice belongs to the designer.

RCD type. Type AC detects alternating current only; Type A also pulsating current with DC components; Type F suits single-phase inverters and frequency converters; Type B also detects smooth DC residual current (Protection against earth faults with Residual Current Devices (Technical guide, 2015)). Inverters, battery systems, chargers and motor drives make the choice matter. In New South Wales, Australia, circuits fed by a back-up battery need Type A RCDs, at most 30 mA in homes; Type AC does not comply there (Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025).

National codes, as examples. BS 7671 in the United Kingdom (Mythbusters 8: Socket-outlets must be protected by a 30 mA RCD (Wiring Matters, Issue 91, July 2022)); AS/NZS 3000 in Australia and New Zealand (Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025); NFPA 70, the National Electrical Code, in the United States (NFPA 70, National Electrical Code (NEC)). Equipment sold in the European Union falls under the Low Voltage Directive (Low Voltage Directive 2014/35/EU).

Settled, open, contested

Settled. Protection against shock is never omitted to save cost. 30 mA additional protection for sockets is required across the codes read here.

Open. RCD type selection as inverter-fed and DC-coupled equipment spreads; codes are being amended region by region (Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025).

Contested. Whether every socket should have 30 mA protection. The IET states that adding it everywhere can be unhelpful to users and allows a documented exception (Mythbusters 8: Socket-outlets must be protected by a 30 mA RCD (Wiring Matters, Issue 91, July 2022)); Australia requires it on all domestic final subcircuits (Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025).

The four stages

Resources at each stage

4 Deploy

Install, run and measure

Open Add a resource

What changes between 30 adults and 300 people

For 30 adults on one site, one installation and one certificate; the earthing arrangement is decided once. For 300 people across many buildings, each building is its own installation with its own certificate, the network between them needs sectioned protection, and a named responsible person keeps the records. RCDs should be split across circuits so that normal leakage does not trip whole buildings (Mythbusters 8: Socket-outlets must be protected by a 30 mA RCD (Wiring Matters, Issue 91, July 2022)).

Reference designs

Open for contributions Designs with drawings, specifications and a bill of materials. Add to it

Parts list

Every resource that supports this element. Those marked External carry the label “External resource. Not made or verified by Public Protocol”.

ResourceTypeOriginMaturitySafetyLicence, as stated at its source
Protection against earth faults with Residual Current Devices (Technical guide, 2015)GuideExternalEstablishedS3Not stated on the page opened
Low Voltage Directive 2014/35/EUStandardExternalEstablishedS2Not stated on the page opened
IEC 60364-5-52:2009+AMD1:2024 Low-voltage electrical installations - Part 5-52: Selection and erection of electrical equipment - Wiring systemsStandardExternalEstablishedS3Copyright © IEC 2026. All rights reserved
IEC 61140:2016 Protection against electric shock - Common aspects for installation and equipmentStandardExternalEstablishedS3Not stated on the page opened
Mythbusters 8: Socket-outlets must be protected by a 30 mA RCD (Wiring Matters, Issue 91, July 2022)GuideExternalEstablishedS3© 2026 The Institution of Engineering and Technology
Lessons In Electric CircuitsGuideExternalEstablishedS0Creative Commons License (variant not named on the page)
NFPA 70, National Electrical Code (NEC)StandardExternalEstablishedS3Not stated on the page opened
Residual Current Device (RCD) protection in Battery Energy Storage Systems (BESS), advisory note 3/2025GuideExternalEstablishedS3Copyright © 2026

Depends on, and completes

Depends on 5.4.

It is one of 23 elements that complete Energy.

The standing questions

Who pays for a qualified designer and inspector. Who is the named responsible person. Who decides when a circuit is disconnected for safety.

Environments

Islands and coasts. No source found for installation-specific rules; see enclosures in the harsh-settings notes of the battery and motor proposals. Arctic cold. No source found for installation rules. Hot deserts. No source found. Tropical humid forest. No source found. Temperate forest. No source found. High altitude. No source found for installations; equipment ratings change above 1,000 m (see the motors proposal). Flood plains. No source found. Other harsh settings. Remote sites without a supplier earth rely on local electrodes, where the source states RCDs are compulsory (Protection against earth faults with Residual Current Devices (Technical guide, 2015)).

Safety

State and evidence

Drafted

An editor has written the element's text from the resources listed under it, citing them. It is checked when it is reviewed.

Evidence from a real place or system is recorded here, with what did not work. What the states mean

History